Model | Cooling capacity | Fan quantity | Fan motor | Defrosting method |
DD12 | 2400w | 1 | 1*350mm | Electric defrosting |
Technical requirements:
1. Use hydrophilic aluminum fins. The fin pitch is 6.0mm.
2. The fins are arranged neatly and the expansion tube is tight and not loose.
3. Test pressure 2.5MPa. It is qualified if there is no leakage after being placed in water for 5 minutes.
4. The air return pipe is φ19. The liquid inlet pipe is φ12.
5. Electric heating tube power 4x0.7KW
6. Equipped with a φ350 external rotor motor with a power of 129W and an air volume of 2290m³/h.
7. 9.52 copper tubes and 6 dispensers.
Customized air cooler three features
1: Air cooler with expansion valve
2: Copper air cooler drain interface
3: The air cooler has hinges for easy disassembly.